UPS & Battery Backup Calculator

Size fire alarm standby batteries (BS 5839-1 / NFPA 72) and estimate CCTV & network UPS runtime.

FreeNo sign-upStandards-basedPeukert-corrected

System & standard

min
×
×

Load currents

A
A

Use the panel's quiescent current plus all field devices in standby; alarm current includes sounders, beacons and relays energised.

DeviceQtyStandby mAAlarm mA
Total00

Enter per-device currents from datasheets in mA; totals are converted to A. Include the panel itself as a row.

Battery capacity gauge

Standby vs alarm contribution

Inputs

📘 Worked example

Load

DeviceQtyW eachSub-total
Total0 W

Use real power (W). For PoE cameras, count the camera's PoE draw and the switch's own consumption, or the switch's total input power — not both.

W

UPS

VA
PF
%

Typical 85–92 % on battery. Default 90 %.

Battery bank

Ah
h
%
min

Runtime vs target

Runtime curve (runtime vs load)

Blue curve: estimated runtime of this battery bank at any load. Dot: your load. Dashed green: target runtime. Amber / red verticals: 80 % / 100 % of the UPS W rating.

Inputs

📘 Worked example
🎓 How to use this tool

A · Fire alarm standby battery

  1. Choose the standard (BS 5839-1 or NFPA 72) and the panel battery voltage (usually 24 V = two 12 V batteries in series).
  2. Select the standby period (normally 24 h) and check the alarm duration: 30 min BS, 5 min NFPA, 15 min NFPA with EVACS / voice.
  3. Enter the total standby and alarm currents from the panel datasheet, or switch to Device table and list every device with its mA figures.
  4. Keep the 1.25 ageing factor unless your specification says otherwise; read the required Ah and the next standard battery size.

B · CCTV / network UPS runtime

  1. List the loads (cameras, NVR, switches, routers) in watts, or enter a total.
  2. Enter the UPS VA and power factor, then the battery bank: DC voltage, number of 12 V blocks, Ah each, chemistry and usable %.
  3. Set a target runtime: the tool shows the estimated runtime, the bank Ah needed to reach the target, and warns if the UPS is loaded above 80 %.

Tips & common mistakes

  • Don't mix mA and A: 350 mA = 0.35 A. The device table takes mA, the totals take A.
  • Never pick a battery larger than the panel charger is rated to recharge (BS 5839-1 expects recharge to 80 % within 24 h) — check the panel's maximum battery size.
  • Battery runtime is not linear: doubling the load more than halves runtime on lead-acid (Peukert effect).
  • VA is not W. A 1000 VA UPS at 0.6 PF only delivers 600 W.
  • Batteries in series must be the same type, capacity and age; replace them as a set (typically every 4–5 years for VRLA).

Standards & assumptions

Fire mode: C = (Is × Ts + Ia × Ta) × F, following the BS 5839-1 annex method (F = 1.25) and common NFPA 72 secondary-supply practice (20–25 % safety factor, typical). Standard sizes are matched conservatively (17/18 Ah is treated as 17 Ah, etc.). UPS mode: battery current I = P ÷ (η × V); runtime t = H × (C ÷ (I × H))^k × usable %, Peukert's law at constant power; values marked typical are not normative. Results are for guidance only and must be verified against the panel / UPS / battery manufacturer's data and the applicable local code and authority having jurisdiction.