PoE Budget Calculator

Last reviewed: by Sarwar Islam

Check whether a PoE switch can power everything you plan to plug into it: the total budget, the per-port limit of each PoE standard and the power lost in the cable. Add your cameras, access points and phones with their datasheet maximum power, and the calculator shows the load, headroom and any port that is over its class. A worked 20-device example and the cable-loss method are explained below.

Techubox

PoE Budget Calculator

Check a PoE switch's power budget, port count and per-port class limits, including cable loss, for cameras, APs, phones and readers.

FreeNo sign-upIEEE 802.3af / at / btCable loss included

1 · PoE switch

Calculate by?

Recommended budget = load × (1 + margin). 20% covers start-up surges, IR/heater peaks and ageing.

2 · Powered devices

One row per device type. Use the datasheet maximum power (IR on, heater on), not the typical figure. Each device uses one port.

Switch front panel

≤ 75% of port limit75–100%fault / over limitfree port

PoE budget

Per-device results

    📘 Worked example
    🎓 How to use this tool
    1. Enter the switch model, its total PoE budget in watts (from the datasheet, not the power-supply rating) and the number of PoE ports.
    2. Pick the port standard: 802.3af, 802.3at (PoE+), or 802.3bt Type 3 / Type 4. This sets the per-port limit.
    3. Add one row per device type. Choose a preset or type the device's maximum power from its datasheet, and set the quantity.
    4. Leave Class on Auto or set the class printed on the datasheet. A device that draws more than its class allows is flagged.
    5. Enter the cable length and cable type for each row. Cable loss is added to give the power the switch must supply.
    6. Choose Calculate by: device max power, or class allocation if your switch reserves power by class.
    7. Read the KPIs and verdict. Keep the load inside the green zone of the budget bar, then save, export or print the result.

    Tips & common mistakes

    • Use the camera's max power with IR LEDs and heater on. Night-time IR and cold-start heaters are where budgets fail.
    • The PoE budget is often far below the PSU rating: a "250 W" switch may only have 190 W for PoE. Check the datasheet.
    • Copper-clad aluminium (CCA) cable has about 1.6× the resistance of copper. It increases loss and is not standards-compliant for PoE.
    • A 60 W heater PTZ needs an 802.3bt Type 4 port (or a midspan/injector). It will not run on PoE+.
    • Over 100 m, use a PoE extender or a fibre link with a local PoE switch.

    Standards & assumptions

    IEEE 802.3af-2003, 802.3at-2009 and 802.3bt-2018 (now part of IEEE 802.3) PSE and PD class powers; ANSI/TIA-568 and ISO/IEC 11801 (100 m channel, 90 m permanent link). Cable loss is P = I²R at the minimum PSE voltage (44 V af, 50 V at/bt Type 3, 52 V bt Type 4), with conductor DC resistance at 20 °C of 9.38 Ω/100 m for 24 AWG (TIA maximum) and 7.33 Ω/100 m for 23 AWG (typical). 2-pair powering is assumed up to Class 4 and 4-pair for Classes 5–8. Per-pairset current limits of 350 / 600 / 600 / 960 mA are typical. Higher temperatures and bundled cables increase resistance. Device powers in the presets are typical; use your datasheet. The result is for guidance only and must be verified against the manufacturer's data and local code.

    Techubox Engineering Tools · techubox.com/tools

    To download and print this tool without a watermark, please log in and request approval.

    Why PoE budgets fail on site, not on paper

    Most PoE designs look fine on paper. Trouble starts at night, when IR LEDs switch on, in winter, when PTZ heaters start, and on long cable runs, where some of the power never reaches the device. This calculator adds those effects in. It checks three things for every switch: that the total load stays inside the PoE budget with a safety margin, that each device fits the per-port limit of the standard (802.3af, 802.3at or 802.3bt), and how much power the cable itself burns. It is for installers choosing a switch and consultants checking a contractor’s selection.

    How to use it

    1. Enter the switch’s PoE budget in watts from the datasheet (not the power supply rating) and the number of PoE ports.
    2. Choose the port standard. This sets the per-port limit, for example 30 W at the switch for 802.3at (PoE+).
    3. Add one row per device type: a preset or a custom device, the quantity and the maximum power from the datasheet. Leave the class on Auto unless the datasheet states one.
    4. Enter the cable length and type for each row.
    5. Choose how the switch allocates power: by the device’s actual maximum (most managed switches) or by class (switches that reserve the full class power per port).
    6. Read the load, headroom and per-device table, then save or print.

    Worked example: 24-port PoE+ switch for a car park

    A 24-port 802.3at switch with a 370 W PoE budget feeds a car park and its entrance building. All cabling is Cat6 23 AWG, and the safety margin is 20 %.

    Device Qty Max power Cable Class Power at port Row total
    IR dome camera 16 8 W 60 m 3 8.12 W 129.9 W
    PTZ camera 2 24 W 85 m 4 25.64 W 51.3 W
    Wi-Fi 6 access point 2 13 W 40 m 4 13.20 W 26.4 W

    The total load is 207.5 W, 56 % of the 370 W budget (56.1 % exactly), with 162.5 W of headroom and 20 of 24 ports used. With the 20 % margin, the recommended minimum budget is 249.0 W and the safe load for this switch is 308.3 W, so the selection passes. Notice where the cable loss sits: each dome loses only 0.12 W on 60 m, but each PTZ loses 1.64 W on 85 m, because loss rises with the square of the current.

    Now switch the calculation to class allocation. The same devices reserve 16 × 15.4 W plus 4 × 30 W = 366.4 W, which is 99 % of the budget and far beyond the 308.3 W safe load. On a switch that reserves power by class, this design needs a bigger budget or fewer devices per switch. Check the switch’s power management mode before signing off.

    How the numbers are worked out

    • The device draws PPD = V × I − I²R, where V is the minimum PSE voltage (44 V for 802.3af, 50 V for 802.3at and 802.3bt Type 3, 52 V for Type 4) and R the loop resistance of the powered pairs.
    • Solving for I gives I = (V − √(V² − 4 × R × PPD)) ÷ (2R). The port must then supply PPSE = PPD + I²R.
    • Conductor resistance at 20 °C is taken as 9.38 Ω per 100 m for 24 AWG (the TIA maximum) and 7.33 Ω per 100 m for 23 AWG (typical). Two-pair powering is assumed up to Class 4 and four-pair for Classes 5 to 8.
    • For one PTZ in the example: R = 0.0733 × 85 = 6.23 Ω, I ≈ 0.51 A, loss ≈ 1.64 W, port power 25.64 W, inside the 30 W PoE+ limit.

    Design tips and common mistakes

    • Use maximum power, not typical. Camera datasheets give both. The maximum, with IR and heater on, is the one that trips a port at 2 a.m.
    • Heated PTZs need 802.3bt. A 60 W heater PTZ will not run from a PoE+ port; use a Type 4 port or a midspan injector.
    • Avoid copper-clad aluminium cable. CCA has roughly 1.6 times the resistance of copper, so loss and heating go up and the cable does not meet the cabling standards for PoE.
    • Do not stretch beyond 100 m. Use a PoE extender or a fibre link to a local switch instead.

    Limits of the calculator

    The cable model uses DC resistance at 20 °C. Hot ceilings and large bundles raise resistance and loss, and some switches reduce their PoE budget at high ambient temperature or when one power supply fails. Patch cords count only if you include them in the length, vendor-specific schemes are not modelled, and device presets are typical values. Treat the result as a design check and confirm it against the switch and device datasheets.

    Standards note

    The class powers come from IEEE 802.3af, 802.3at and 802.3bt, now consolidated in IEEE 802.3. ANSI/TIA-568 and ISO/IEC 11801 give guidance on the 100 m channel and on cable bundling for remote powering. Check the edition your project specification refers to.

    Frequently asked questions

    Is the PoE budget the same as the switch’s power supply rating?

    No. A switch with a 250 W power supply may offer only 190 W for PoE, because the switch itself uses part of it. Always enter the PoE budget from the datasheet.

    How much safety margin should I keep?

    20 % is a common choice. It covers start-up surges, IR and heater peaks and ageing. In the example it raises the recommended budget from 207.5 W to 249.0 W.

    Why does a longer cable need more power at the switch?

    Cable resistance turns part of the power into heat, so the switch must supply more to deliver the same watts at the far end.

    Which method should I choose, device power or class?

    Use device maximum power for switches that allocate dynamically. Choose class allocation if the switch reserves the full class power per port; it is the more conservative check.

    Related reading: Cat5e vs Cat6 vs Cat6A vs Cat7, VLANs for CCTV systems and the CCTV installation and wiring guide.

    Watch the tutorial

    PoE Budget Calculator: step-by-step tutorial

    PoE Budget Calculator: step-by-step tutorial · More on YouTube @techubox