Fire Alarm Design Tool

Last reviewed: by Sarwar Islam

🔥 Learning path · Step 9 of 14
Fire Alarm Engineer

Plan an addressable fire alarm system on your own floor plan: place detectors to BS 5839-1 or NFPA 72 spacing, add call points, sounders and interface modules, number the loops and size the standby batteries. The worked example and design notes below explain what the tool calculates and where your judgement takes over.

Fire Alarm Design Tool v2.1

Load your drawing (PDF, image, DXF or DWG), draw rooms, auto-place smoke and heat detectors to BS 5839-1 or NFPA 72, add call points and sounders, check coverage gaps, address loops, and export the device schedule and BOQ.

Drawing units
Set drawing scale
Real length between the two points:

Standard

Place device (tap the plan)

I/O module by interface

Sounders & spacing

Panels & network

Battery (standby power)

Loops & display

Rooms (0)

Export
Exported plan

How to use: 1) Load your plan (PDF, PNG, JPG, DXF or DWG) and set the scale on a known dimension. DXF/DWG set the scale from the drawing units, and you can hide layers such as furniture or text. 2) Draw each room or corridor as a rectangle and set its ceiling height and detection type. 3) Auto-place fills each room with the fewest detectors on an even grid so every point is within the coverage radius: BS 5839-1 smoke 7.5 m and heat 5.3 m; NFPA 72 0.7 × spacing (smoke 9.1 m → 6.4 m; heat per listed spacing, reduced for ceilings over 3 m). Red dots show uncovered points. 4) Add call points at exits and on escape routes (BS 5839-1:2025: 45 m travel / 30 m straight line; NFPA 72: within 1.5 m of each exit, 61 m travel), sounders, beacons, modules and the panel. 5) Address loops numbers devices from the panel and estimates cable per loop. Flat, smooth ceilings assumed: beams, slopes, airflow, voids and stairs need the designer's judgement. Design aid only; confirm with the standard, the product datasheets and the authority having jurisdiction (in KSA, SBC 801 / Civil Defense). Techubox.com


To download and print this tool without a watermark, please log in and request approval.

What the addressable Fire Alarm Design Tool is for

On an addressable system every device has its own address on a loop, so the panel can report “smoke detector 1.023, server room” instead of “zone 3”. The design questions change as a result: how many devices fit on a loop, where the short-circuit isolators go, how long the loop cable is, how much current the loop draws in alarm and what battery the panel needs. This tool answers those first-pass questions on a real drawing. It is used by fire alarm contractors preparing tender drawings, consultants checking a layout before coordination meetings and engineers who want a quick bill of quantities.

Workflow in six steps

  1. Load the plan (PDF, image, DXF or DWG) and set the scale. With DXF/DWG you can hide furniture and text layers.
  2. Choose BS 5839-1 or NFPA 72, then pick the panel and the device brand from the libraries.
  3. Draw each room, set its ceiling height and detection type, and press Auto-place all.
  4. Place manual call points, sounders, sounder beacons, beacons and I/O modules (flow switches, tamper switches, AHU shutdown, lift homing, door release and so on).
  5. Press Address loops. Devices are numbered from the panel, isolators are added and loop cable is estimated.
  6. Open the battery section and the BOQ, then export the device schedule and BOQ as CSV, save the project or print.

Worked example: an 1,800 m² office floor on one loop

The test floor has two open offices (30 × 20 m and 24 × 20 m), a 60 × 2 m corridor, a server room, two meeting rooms, a store, a kitchen with an A1/rate-of-rise heat detector, a plant room with fixed heat detection and a 24 × 8 m reception covered by multi-sensors. All ceilings are 3 m and the standard is BS 5839-1.

  • Detection placed by the tool: 20 smoke, 2 multi-sensor, 2 heat A1/RoR and 2 fixed heat detectors. Each open office took 6 smoke detectors and the corridor took 4, spaced to the corridor rule.
  • Manual devices added: 6 call points, 8 sounders, 3 sounder beacons and 3 I/O modules, plus the panel.
  • Address loops result: 46 devices on Loop 1 with about 406 m of 2-core 1.5 mm² fire-resistant cable, and 4 short-circuit isolators (panel out, panel return and one every 20 devices).
  • Battery: standby 162 mA, alarm 681 mA. The tool’s BS 5839-1 formula gives 1.25 × (24 h × 0.162 A + 1.75 × 0.681 A × 0.5 h) = 5.6 Ah, so the suggestion is 2 × 12 V 7 Ah in series.

Two points stand out. 46 devices is far below a typical 125-device loop limit; on large floors loop current or cable length usually limits first, and the panel maker’s loop calculator must confirm it. And 7 Ah is the smallest standard battery that fits, with little spare. If a second floor may follow, specify the next size up now and check the charger rating.

Formulas and assumptions

  • Coverage radius: BS 5839-1 smoke 7.5 m and heat 5.3 m; NFPA 72 uses 0.7 × the listed spacing (smoke 9.1 m gives 6.4 m), reduced for heat detectors on ceilings above 3 m.
  • Call point reach: 45 m travel or 30 m straight line for BS 5839-1 in the current tool; NFPA 72 within 1.5 m of each exit and 61 m travel.
  • Isolators: one at the panel output and return, then one per 20 devices. Skip them if every device has a built-in isolator.
  • Loop cable: the routed length plus a drop per device and a spare percentage (10 % default).
  • Battery: 1.25 ageing factor × (24 h standby + 30 min alarm with a 1.75 alarm factor) for BS mode; NFPA mode uses its own alarm time and margin fields.

Design tips from site work

  • Address the loop in the order the cable will actually be pulled. A tidy schedule that the installer cannot follow costs a day of commissioning.
  • Put an isolator either side of every fire compartment boundary, not only every 20 devices. One cable fault should never take out two compartments.
  • Count I/O modules early. Lift homing, smoke dampers, access control release and pressurisation fans often double the module count late in a project; the fire alarm integration guide lists the usual interfaces.
  • For tall buildings plan the network and riser first; see fire alarm design for high-rise buildings.

Limits of the tool

The layout assumes flat ceilings without beams, voids or strong airflow. It does not calculate loop voltage drop against the panel’s loop calculator, sounder audibility in each room, cause-and-effect or the system category. Device currents are datasheet values where confirmed and typical values elsewhere. Treat the result as a well-organised draft for a competent designer to check, not a finished design.

Standards note

BS 5839-1, NFPA 72 and the EN 54 product standards give guidance on spacing, call points, isolation, zoning and standby power. They differ from each other and change between editions, so always confirm the edition in your specification and the requirements of the local authority or AHJ before issuing drawings.

Frequently asked questions

Is this a replacement for a certified design?

No. It speeds up layout and checks, but the final design must follow the standard, the device datasheets and the authority having jurisdiction (in Saudi Arabia, SBC 801 and Civil Defense).

Which device currents are used?

Datasheet values where confirmed, and typical values elsewhere. Always check the datasheet of the exact model you will install.

Can I design more than one panel?

Yes. You can network several panels and the addresses are numbered per panel and loop.

Why does the tool add isolators every 20 devices?

It is a common design rule so that a short circuit removes only a small section of the loop. Your panel maker or specification may ask for fewer devices between isolators.

Troubleshooting a live system rather than designing a new one? Start with the addressable fire alarm fault guide.