Access Control Designer
Last reviewed: by Sarwar Islam
Draw an access control system as a riser or single-line diagram: readers, locks, exit devices, controllers, power supplies, parking equipment and the interfaces to fire alarm, CCTV and lifts. As you connect devices, the tool runs design checks and works out PSU load, battery size, cable totals and voltage drop. Below the designer, the built-in sample project is worked through number by number.
To download and print this tool without a watermark, please log in and request approval.
From door schedule to riser, with the checks built in
Access control drawings tend to go wrong in the same places: an EM lock with no way out, an escape door that stays locked when the fire alarm operates, a 12 V supply quietly loaded to 95 %, or a reader 200 m from its controller on Wiegand cable. This designer knows those traps. You place devices, group each door’s hardware into a door zone, connect everything with real cable types, and the Checks, Calculations and BOQ tabs update as you go. It suits ELV engineers, integrators, estimators and consultants preparing a riser, door schedule or tender quantities, and students learning how a door is wired.
Working through a project
- Set the title block and, under Design settings, the battery target in hours (4 h by default) and the cable allowance (10 % by default).
- Place controllers and power supplies, then build each door with the Door wizard or by dragging a lock, reader, exit button, door contact and closer from the library.
- Select a door’s devices and group them as a door zone. In its properties, set leaf, material and the two separate options: escape-route door and fire-rated door.
- Draw the cables and interfaces (fire alarm relay, lift, NVR, server). Pick a type (lock power, Wiegand, OSDP / RS485, Cat6, REX, door contact, relay, fire-rated) or leave it on Auto.
- Clear the Checks tab, review Calculations, then export the drawing (PNG, SVG or PDF) and the BOQ as CSV.
Escape-route door and fire-rated door are different questions
Version 1.0.1 keeps these as two independent ticks, because a door can be either, both or neither. Escape-route door is about getting people out: the checks flag a fail-secure lock and an escape door lock with no break glass and no fire alarm release on its power circuit. Fire-rated door is about the door set holding back fire: the tool reminds you that the lock, bracket, closer and any glazing or cable entry must suit that tested fire door set. A glass main entrance is often an escape door but not fire-rated; a server room door is often the reverse.
Worked example: the built-in sample office
Load sample project opens a six-door project: D-01 main entrance (double glass leaf, escape route, double EM lock with U brackets, face terminal, break glass, no-touch exit button), D-02 server room (fail-secure mortise lock, fingerprint terminal and MIFARE readers in and out), three offices with 280 kg EM locks, and a staff car park with a boom barrier, UHF reader, ANPR camera and loop detector. A 2-door and a 4-door controller and a lift floor controller are fed from two 12 V 5 A supplies, each with one 17 Ah battery. The summary reads 42 devices, 6 door zones and 42 cables totalling 1,167 m (1,284 m with the 10 % allowance), and the Checks tab reports no issues.
| Calculation | PSU-01 | PSU-02 |
|---|---|---|
| Connected load | 3.09 A | 3.22 A |
| Load vs 5 A rating | 62 % | 64 % |
| Battery needed for 4 h (I × t ÷ 0.8) | 15.5 Ah | 16.1 Ah |
| Installed / backup achieved | 17 Ah / 4.4 h | 17 Ah / 4.2 h |
The biggest loads on PSU-01 are the double EM lock and the face terminal at 1,000 mA each; on PSU-02, three EM locks at 500 mA and the UHF reader at 800 mA. Both pass, but PSU-02 has little room: one more 500 mA EM lock would make it 3.72 A × 4 h ÷ 0.8 = 18.6 Ah, more than the 17 Ah fitted. The worst voltage drop is on the 32 m, 1.0 mm² run to EM-04: 2 × 32 × 0.5 × 0.0175 ÷ 1.0 = 0.56 V, or 4.7 % of 12 V, inside the tool’s 10 % limit.
Formulas and limits used by the checks
- PSU load = sum of device currents fed from that supply; a warning above 80 % of rating and an error above 100 %.
- Battery Ah = load (A) × backup hours ÷ 0.8; backup achieved = installed Ah × 0.8 ÷ load.
- Voltage drop ΔV = 2 × L × I × ρ ÷ A with copper at 0.0175 Ω·mm²/m; warning above 10 % of supply.
- Typical length limits: Wiegand 150 m, RS485 1,200 m, Cat6 channel 100 m.
Design tips
- Replace library currents with datasheet figures at your supply voltage; EM locks and terminals vary widely.
- Keep supplies below about 80 % so a future door does not force a new PSU.
- Agree the cause-and-effect for each escape door early: which doors release on fire alarm, and from which panel output. The fire alarm integration guide lists the usual interfaces.
- For long reader runs or new projects, consider OSDP over RS485 instead of Wiegand; see Wiegand vs OSDP.
What the tool does not do
It does not place hardware on a floor plan, check software licence capacity, or confirm that a product suits a fire door set. Currents are typical catalogue values, and passing the checks is not a code review; a competent engineer approves the final design. For background on each component, see access control system components.
Standards note
BS 7273-4 gives guidance on the actuation of door release mechanisms by the fire alarm system, NFPA 101 and SBC 801 cover means of egress, and the EN 60839-11 series covers electronic access control systems. Requirements differ between countries, so check the current edition and your local authority or AHJ before issuing drawings.
Frequently asked questions
Why is my escape door flagged as an error?
Its lock is fail-secure, or its lock power has no break glass and no fire alarm release.
Should every escape door be marked fire-rated?
No. Tick fire-rated only if the door itself is a fire door set; it is a separate question from escape.
Where is my project saved?
In your own browser only. Use Save project (.json) to keep a copy or move it to another computer.
Watch the tutorial

Access Control Designer: step-by-step tutorial · More on YouTube @techubox