Voltage Drop Calculator

Last reviewed: by Sarwar Islam

Find the voltage drop, the voltage at the last device and the smallest cable that works for 12, 24 and 48 V DC circuits and 230 V single-phase feeds. It is built for fire alarm sounder circuits, CCTV and access control power runs, with an option to test at end-of-discharge battery voltage. Below the tool, a sounder circuit is worked through on 1.5 mm² and 2.5 mm² cable.

Techubox

Voltage Drop Calculator (12/24 V DC & 230 V AC)

Cable voltage drop, end-of-line voltage and minimum conductor size for fire alarm sounder circuits, CCTV and access control power, and 230 V single-phase feeds.

FreeNo sign-upIEC 60228 conductor dataDaisy-chain mode

⚡ Supply

V
Treated as DC / resistive load (2-wire loop).
Fire alarm panels must work on standby batteries; test the worst case at end of discharge (typical 1.75 V/cell lead-acid).

🧵 Cable

mm²
Ω/km
m
Loop resistance uses 2 × this length.
Length = distance of the last device in the daisy-chain list.
°C
Rt = R20 × (1 + α(t − 20)); α = 0.00393 Cu, 0.00403 Al. Hot ceiling voids and fire-resistant cable runs are often 30–50 °C.

💡 Load

Load distribution
A
W
I = P / V (× PF for AC), at the supply voltage. Constant-power loads (PoE switches, DC-DC converters) draw more at low voltage, so keep a margin.
1.0 for resistive loads; LED drivers are typically 0.9–0.95.
mA
Use the alarm (worst-case) current from the datasheet at the lowest volume/flash setting you will not exceed.
Unticked: the ½ rule for a load spread evenly along the cable. Ticked is slightly more conservative.
#Distance from PSU (m)Current (mA)Remove
Distances are cumulative cable distance from the supply, not spacing. Max 200 devices.

🎯 Limits

%
V
0 = don't check. Many 24 V sounders/beacons are rated down to about 16–17 V (typical; check the datasheet).

📈 Circuit & voltage profile

🔔 Voltage at each device

Inputs

🧮 Calculation steps for your inputs
📘 Worked example
🎓 How to use this tool
  1. Pick the system voltage. For a fire alarm circuit on batteries, tick end-of-discharge battery voltage to test the worst case (21.0 V on a 24 V system).
  2. Choose the conductor size (mm² or AWG) and material. Use Custom with the datasheet Ω/km for unusual cables.
  3. Enter the one-way cable length: the route distance from the supply to the far end. Do not double it; the tool does.
  4. Choose how the load sits on the cable: at the end (one camera, one lock), evenly spread (sounders on a loop-less radial circuit), or daisy chain to list each device's distance and current.
  5. Enter the load as total amps, watts, or mA per device × number of devices. Use alarm current for sounders and inrush/heater current for cameras with heaters.
  6. Set the allowed drop % and the device minimum voltage. The tighter of the two governs.
  7. Read the verdict, then use Max length and Min conductor size to fix a failing circuit. Save or print the result for your submittal.

Tips & common mistakes

  • Entering the loop length as the one-way length doubles the result. Enter the route distance only.
  • Checking at 24 V nominal hides failures: fire alarm devices must still work at the end of the battery standby period.
  • For sounders, use the alarm current at the tone and volume you will commission, not the standby current.
  • Terminal, fuse and connector resistance add to the drop. Keep a margin rather than designing to exactly 100% of the limit.
  • 12 V CCTV over long runs rarely works: the same cable carries 4× the power at 24 V or 48 V for the same drop.

Standards & assumptions

Conductor resistance at 20 °C from IEC 60228 (class 1/2 plain copper; aluminium from 10 mm²). AWG values are typical solid annealed copper (ASTM B258). Aluminium below 10 mm² and custom areas are typical estimates. Temperature correction Rt = R20(1 + α(t − 20)). The 230 V calculation is resistive only (reactance ignored, which is small for ≤ 16 mm²; ΔV = I × Rloop is conservative versus R·cosφ). Typical 230 V limits: 3% lighting, 5% other uses (e.g. IEC 60364-5-52 Annex G / BS 7671 Appendix 4, from the origin of the installation). For fire alarm circuits, check the end-of-line voltage against the device's minimum operating voltage (EN 54-3 / BS 5839-1 practice, NFPA 72 in the US). This result is for guidance only and must be verified against the manufacturer's data and local codes.

Techubox Engineering Tools · techubox.com/tools

To download and print this tool without a watermark, please log in and request approval.

Checking the far end of the cable, not the panel terminals

Every device on a long low-voltage run sees less voltage than the power supply delivers. On a 24 V fire alarm sounder circuit, an access control lock or a 12 V camera, that loss decides whether the last device works reliably. This calculator works out the drop from the conductor resistance, the route length and how the load is spread along the cable, then compares the result with two limits: an allowed percentage drop and the device’s minimum operating voltage. The tighter of the two governs. It is meant for fire alarm and security installers, designers sizing cables for a submittal and commissioning engineers chasing a sounder that will not sound.

Step by step

  1. Choose the system voltage. For battery-backed fire alarm circuits, tick Use end-of-discharge battery voltage so the check runs at 21.0 V on a 24 V system.
  2. Choose the conductor size in mm² or AWG and the material. A custom Ω/km value covers unusual cables.
  3. Enter the one-way route length. The tool doubles it for the return conductor, so do not double it yourself.
  4. Choose the load distribution: at the end (one lock or camera), evenly spread (sounders along a radial circuit) or a daisy chain with each device’s distance and current.
  5. Enter the load as amps, watts or milliamps per device × number of devices.
  6. Set the allowed drop and the device minimum voltage, then read the verdict, maximum length and minimum conductor size.

Worked example: 20 sounder-beacons on a 210 m circuit

A warehouse sounder circuit runs 210 m from the panel and carries 20 sounder-beacons, each drawing 50 mA in alarm at the commissioned tone and flash rate. The specification limits drop to 10 %, and the devices are rated down to 17 V. We test at the 21.0 V end-of-discharge voltage, use the exact factor for 20 equal devices with the last one at the end, and leave temperature at 20 °C.

Value 1.5 mm² copper 2.5 mm² copper
Load current 1.000 A 1.000 A
Resistance at 20 °C 12.10 Ω/km 7.41 Ω/km
Loop resistance (2 × 210 m) 5.082 Ω 3.112 Ω
Voltage drop 2.67 V (12.70 %) 1.63 V (7.78 %)
Voltage at the last device 18.33 V 19.37 V
Max length at this load 165 m 270 m
Verdict Fails the 10 % limit Passes

The allowed drop is the smaller of 10 % × 21.0 V = 2.10 V and 21.0 − 17.0 = 4.00 V, so 2.10 V governs. On 1.5 mm² the drop is 1.000 × 5.082 × 0.525 = 2.67 V, which fails. Note that 18.33 V is still above the 17 V device minimum, so the sounders would probably work; it is the project’s 10 % rule that fails the cable. Moving to 2.5 mm² gives 1.63 V of drop and 19.37 V at the far end, inside both limits. The tool’s other suggestion is to keep the run under 165 m; splitting the devices across two circuits works too.

Formulas behind the result

  • Loop resistance: Rloop = 2 × L × R ÷ 1000, with R in Ω/km from IEC 60228 for copper.
  • Load at the end: ΔV = I × Rloop.
  • Load spread evenly (the ½ rule): ΔV = I × Rloop ÷ 2.
  • N equal devices, last at the end: ΔV = I × Rloop × (N + 1) ÷ 2N. For 20 devices the factor is 0.525, slightly more conservative than the ½ rule.
  • Temperature correction: Rt = R20 × (1 + α(t − 20)), with α = 0.00393 for copper.
  • 230 V circuits are treated as resistive only, which is conservative for small cables.

Field tips

  • Check on batteries, not on mains. A circuit that passes at 24 V can fail at the end of the standby period.
  • Use alarm current at the real setting. Sounder current depends on tone and volume; a beacon’s on its flash rate.
  • Leave a margin. Terminals, fuses and joints add resistance that the calculation does not see.
  • Raise the voltage for long CCTV runs. At 24 V or 48 V the same cable carries far more power for the same drop than at 12 V.
  • Follow the panel maker’s tables. Where the manufacturer publishes circuit-length tables, they take priority.

Limits

The result is a design estimate. Cable reactance, inrush current, conductor heating in bundles and the internal resistance of the power supply are not included. Aluminium below 10 mm², AWG sizes and custom areas use typical values.

Standards note

For fire alarm circuits, EN 54-3, BS 5839-1 and NFPA 72 give guidance on device and power supply performance; common practice is to check the device’s minimum operating voltage at end of battery discharge rather than rely on a fixed percentage. For 230 V installations, IEC 60364-5-52 and BS 7671 give guidance on drop limits, commonly 3 % for lighting and 5 % for other uses. Check the current editions and your local authority or AHJ.

Frequently asked questions

Do I enter the cable length once or twice?

Once. Enter the one-way route distance; the tool adds the return conductor.

Which matters more, the percentage or the minimum voltage?

For fire alarm devices, the minimum operating voltage is the real test. The percentage is often a project rule, and the tool applies whichever is stricter.

Why test at 21.0 V on a 24 V system?

Lead-acid batteries are commonly taken to about 1.75 V per cell at the end of discharge. Devices must still work then, after the standby period.