Voltage Drop Calculator (12/24 V DC & 230 V AC)
Cable voltage drop, end-of-line voltage and minimum conductor size for fire alarm sounder circuits, CCTV and access control power, and 230 V single-phase feeds.
⚡ Supply
🧵 Cable
💡 Load
| # | Distance from PSU (m) | Current (mA) | Remove |
|---|
🎯 Limits
📈 Circuit & voltage profile
🔔 Voltage at each device
Inputs
🧮 Calculation steps for your inputs
📘 Worked example
🎓 How to use this tool
- Pick the system voltage. For a fire alarm circuit on batteries, tick end-of-discharge battery voltage to test the worst case (21.0 V on a 24 V system).
- Choose the conductor size (mm² or AWG) and material. Use Custom with the datasheet Ω/km for unusual cables.
- Enter the one-way cable length: the route distance from the supply to the far end. Do not double it; the tool does.
- Choose how the load sits on the cable: at the end (one camera, one lock), evenly spread (sounders on a loop-less radial circuit), or daisy chain to list each device's distance and current.
- Enter the load as total amps, watts, or mA per device × number of devices. Use alarm current for sounders and inrush/heater current for cameras with heaters.
- Set the allowed drop % and the device minimum voltage. The tighter of the two governs.
- Read the verdict, then use Max length and Min conductor size to fix a failing circuit. Save or print the result for your submittal.
Tips & common mistakes
- Entering the loop length as the one-way length doubles the result. Enter the route distance only.
- Checking at 24 V nominal hides failures: fire alarm devices must still work at the end of the battery standby period.
- For sounders, use the alarm current at the tone and volume you will commission, not the standby current.
- Terminal, fuse and connector resistance add to the drop. Keep a margin rather than designing to exactly 100% of the limit.
- 12 V CCTV over long runs rarely works: the same cable carries 4× the power at 24 V or 48 V for the same drop.
Standards & assumptions
Conductor resistance at 20 °C from IEC 60228 (class 1/2 plain copper; aluminium from 10 mm²). AWG values are typical solid annealed copper (ASTM B258). Aluminium below 10 mm² and custom areas are typical estimates. Temperature correction Rt = R20(1 + α(t − 20)). The 230 V calculation is resistive only (reactance ignored, which is small for ≤ 16 mm²; ΔV = I × Rloop is conservative versus R·cosφ). Typical 230 V limits: 3% lighting, 5% other uses (e.g. IEC 60364-5-52 Annex G / BS 7671 Appendix 4, from the origin of the installation). For fire alarm circuits, check the end-of-line voltage against the device's minimum operating voltage (EN 54-3 / BS 5839-1 practice, NFPA 72 in the US). This result is for guidance only and must be verified against the manufacturer's data and local codes.