Rack Layout & U Planner
Last reviewed: by Sarwar Islam
Lay out a 19-inch cabinet before you order it: list the equipment, let Auto-arrange stack it, and check U space, weight, power, heat and depth in one view. Below the tool, an 18U worked example shows how each figure is calculated and what to watch for on site.
Rack Layout & U Planner
Plan a 19″ cabinet: U space, weight, power, heat and depth, with a drawn front elevation you can export.
1 · Rack
2 · Equipment
Pos U = lowest U the device sits in (1 = bottom). Leave blank and press Auto-arrange. Power: enter what the device draws inside the rack.
Rack elevation · front view
Drag a device up or down to reorder it (desktop). On mobile use ▲ ▼ in the equipment list.
Equipment schedule
Inputs
📘 Worked example
🎓 How to use this tool
- Pick the rack size, width and depth, and choose floor-standing or wall-mount. The load rating switches to a typical value (600 kg floor or 60 kg wall), so change it to your rack's datasheet figure.
- Add each device. Pick a type to fill in a typical height, depth, weight and power, then edit the name and figures from the device datasheet.
- Press ⚡ Auto-arrange. The UPS and heavy kit go to the bottom, the ODF goes to the top, and each switch gets a patch panel and cable manager above it.
- Fine-tune: type a Pos U, drag devices in the drawing (desktop) or use ▲ ▼ (mobile). Overlaps and devices outside the rack turn red.
- Read the tiles: U fill, recommended size at your spare %, weight vs rating, power and heat in BTU/h, and the depth check.
- Export the elevation as PNG for drawings and submittals, save the project, or print / save as PDF.
Tips & common mistakes
- Keep 25–30% of the U space free. Racks always grow, and cramped racks run hot.
- Heavy UPS and battery packs go at the bottom to keep the centre of gravity low. Never wall-mount a UPS heavier than the wall bracket and wall can safely hold.
- A 600 mm deep cabinet will not take most servers (≈ 650–750 mm). Check depth before ordering.
- For heat, count what the device dissipates in the rack. PoE power sent to cameras is dissipated at the cameras, so using the switch's full input is conservative.
- Fill unused U with blanking panels so hot exhaust doesn't loop back to the front.
Standards & assumptions: 19″ rack per EIA-310 / IEC 60297 (1U = 44.45 mm, 482.6 mm panel width). Cabling space practice per TIA-569 / ISO/IEC 14763-2. Heat: 1 W = 3.412 BTU/h. Device sizes, weights, power, load ratings and the 100 mm clearance are typical values. The result is for guidance only and must be verified against the manufacturer's data and local code.
Techubox Engineering Tools · techubox.com/tools
To download and print this tool without a watermark, please log in and request approval.
Why plan a rack on paper first
Most rack problems are found on the day of installation: the UPS is deeper than the cabinet, the patch panels end up far from the switches, or a “22U is plenty” cabinet has no room left for the second NVR the client adds a month later. This planner draws a front elevation from your equipment list and checks it against the cabinet you have chosen. It suits ELV and network contractors preparing a rack layout drawing for a submittal, consultants checking a contractor’s proposal, and site engineers deciding between two cabinet sizes. The PNG, PDF and JSON exports let you drop the elevation straight into a drawing set or keep the project for later.
How to use the planner
- Set the cabinet: rack size in U, width (800 mm adds side cable space), depth, floor-standing or wall-mount, and the static load rating from the maker’s data.
- Enter your spare-capacity target and the front plus rear clearance. The clearance is taken off the depth to give the usable depth for equipment.
- Add each device from the list and adjust its height, depth, weight and the power it draws inside the rack.
- Leave Pos U blank and press ⚡ Auto-arrange, or type positions yourself (1 is the bottom U). Drag devices on the elevation or use ▲ ▼ on mobile to fine-tune.
- Read the result cards and the verdict line, then export the elevation and the equipment schedule.
Worked example: a security and network cabinet in 18U
A small building needs one cabinet for CCTV and the building LAN. The equipment is the tool’s demo list: a 24-core fibre ODF, two 24-port Cat6 patch panels, two 1U cable managers, a 24-port PoE switch, a 24-port core switch, a 32-channel 4-bay NVR (2U), a 2 kVA UPS (2U), an 8-way PDU and a 1U shelf for the ISP’s ONT. That is 13U in total. The demo opens in a 22U cabinet; we change the rack size to 18U (600 × 600 mm, floor-standing, 600 kg rating, 25 % spare target, 100 mm clearance) and press Auto-arrange.
| Check | Result |
|---|---|
| U used | 13 of 18U, 72.2 % fill |
| Free space | 5U, 27.8 % spare |
| Recommended size | 18U (13 ÷ 0.75 = 17.3U needed) |
| Weight | 54.0 kg, 9 % of the 600 kg rating |
| Power and heat | 455 W, 1,552 BTU/h |
| Depth | Deepest item 450 mm (UPS), usable 500 mm |
Auto-arrange puts the fibre ODF at U18, then interleaves patch panel A (U17), a cable manager (U16) and the PoE switch (U15), followed by patch panel B (U14), the second manager (U13) and the core switch (U12). The heavy items go to the bottom: UPS at U1–2, PDU at U3, NVR at U4–5 and the ONT shelf at U6. U7 to U11 stay free in the middle for growth. The verdict reads “The 18U rack works”. Try 15U instead and only 2U (13.3 %) stays spare, below the 25 % target, so the verdict changes to “Workable with notes” and recommends 18U.
The arithmetic behind the cards
- 1U = 44.45 mm (1.75 in). Usable U is set by the mounting rails, not the external cabinet height.
- Recommended size: the smallest standard rack N with N ≥ U used ÷ (1 − spare). Here 13 ÷ 0.75 = 17.3, so 18U.
- Weight: the sum of all device weights, 2.5 + 1.2 + 1.2 + 0.8 + 0.8 + 5 + 4 + 9 + 25 + 1.5 + 3 = 54.0 kg, compared with the load rating (green up to 80 %).
- Heat: watts × 3.412 = BTU/h, so 455 W gives about 1,552 BTU/h.
- Depth: usable depth = cabinet depth − clearance = 600 − 100 = 500 mm. Any device deeper than that is flagged in red.
Practical tips
- Put the UPS and other heavy items low. It keeps the centre of gravity down and makes the cabinet safer to move.
- Pair each patch panel with its switch and a cable manager, as Auto-arrange does. Short, tidy patch cords are easier to trace and keep airflow clear.
- For heat, use what the device dissipates in the cabinet. PoE power delivered to cameras is turned into heat at the cameras, so a PoE switch’s full input rating is a conservative figure. Size the camera load with the PoE budget calculator.
- Check NVR depth with the drives fitted and the cables plugged in. The NVR guide explains why bay count drives chassis size.
- Fill empty U with blanking panels so hot exhaust does not loop back to the front intakes.
- On a wall cabinet, check the wall and fixings as well as the cabinet rating; 60 kg is typical for wall cabinets.
Limits
Default weights, depths and power figures are typical values for common equipment, not your exact models. The planner does not model side-mounted (0U) PDUs beyond noting them, rail adjustment, airflow direction, cooling capacity of the room or cable bend radius at the rear. It also does not design the horizontal cabling feeding the panels; the Structured Cabling Designer sizes panels and switches from the outlet count.
Standards notes
The 19-inch format and the 44.45 mm unit come from EIA-310 and IEC 60297, which give guidance on rack and panel dimensions. TIA-569 and ISO/IEC 14763-2 give guidance on telecom room space and cabling practice. Check the current edition your specification calls up, the cabinet maker’s data and any local authority (AHJ) requirements for floor loading and electrical installation.
Frequently asked questions
How tall is a 1U device?
44.45 mm. An 18U cabinet therefore has 800 mm of rail space, and a 42U cabinet about 1,867 mm.
How much spare space should a rack have?
A target of 20 to 30 % is common. The tool uses 25 % by default; set what the specification requires.
Why is my device flagged as too deep?
Its depth is greater than the cabinet depth minus the clearance you entered. Choose a deeper cabinet or check the device’s real depth including connectors.
Does the heat figure include PoE cameras?
Only what you enter as the device’s power. Enter the power dissipated inside the rack for a closer figure.
Watch the tutorial

Rack Layout & U Planner: step-by-step tutorial · More on YouTube @techubox