Cable Size Calculator & AWG to mm² Converter

Last reviewed: by Sarwar Islam

Pick a cable size from the load current, the route length and the voltage drop you can accept. The calculator works for 12, 24 and 48 V DC, 230 V single-phase and 400 V three-phase circuits, shows the metric (mm²) and AWG answer side by side, and draws the cable so you can see what you are ordering. It checks both the voltage drop and the current rating of multicore copper cable for the way it is installed; protection, fault level and earth loop impedance are separate checks.

Techubox

Cable Size Calculator & AWG ↔ mm² Converter

Four quick steps give the smallest cable that passes both the voltage drop and the current rating, in mm² and AWG.

FreeNo sign-upVoltage drop + current ratingmm² & AWGLive cable drawing
System
Load
A
W
m
Allowed voltage drop
%
⚙ Advanced options

Defaults suit most jobs. Change them to match your cable and site.

Cable

Site

Load & protection

A

Checks

🔍 Your cable

Cable cross-section
What the layers are

    Conductor size is to scale; insulation and sheath are typical proportions only.

    📊 Details: mm² vs AWG, current rating, notes

    Metric and AWG side by side

    Current rating check

    🧮 Calculation steps

    🔁 AWG ↔ mm² converters

    AWG → mm²

    mm² → AWG

    mm²

    Two separate converters: AWG and mm² numbers never mean the same size. 14 AWG is 2.08 mm², not 2.5 mm².

    📋 AWG ↔ mm² conversion table

    Diameter and area are for a solid round conductor (ASTM B258 formula). Copper resistance is ρ/A at 20 °C for solid annealed copper (100% IACS). Stranded wire of the same AWG is slightly thicker and a few percent higher in resistance. “Next metric up” is the smallest IEC 60228 size with at least the same area.

    Metric sizes with the nearest AWG

    🎓 How to use this tool
    1. Tap the system: 12, 24 or 48 V DC, 230 V single-phase or 400 V three-phase.
    2. Enter the load in amps, or switch to watts.
    3. Enter the one-way cable length from the supply to the load.
    4. Pick the allowed voltage drop: 3%, 5% or your own figure.
    5. Read the answer. It updates as you type and says whether voltage drop or current rating set the size.
    6. Open Advanced options when the cable or site differs from the defaults: copper, PVC 70 °C, clipped direct, 40 °C ambient, one circuit, power factor 0.9 on AC, current rating checked.

    Standards & assumptions

    Metric conductor resistance: IEC 60228 maximum DC resistance at 20 °C, class 1/2 plain copper, aluminium from 10 mm². AWG and kcmil sizes from the ASTM B258 formula, resistance = ρ/A with ρ = 0.017241 Ω·mm²/m (copper) or 0.028264 Ω·mm²/m (aluminium, typical). Temperature correction Rt = R20(1 + α(t − 20)) with α = 0.00393 (Cu) and 0.00403 (Al); “Auto” uses 70 °C for PVC and 90 °C for XLPE. Voltage drop ΔV = k × I × L × R / 1000 on DC, with k = 2. On AC the drop is ΔV = k × I × L × (R cos φ + X sin φ) / 1000, with k = 2 single-phase and √3 balanced three-phase (line-to-line), and the reactance taken from the x values of BS 7671 Appendix 4 Tables 4D2B (PVC) and 4E2B (XLPE) from 25 mm²; below 25 mm² those tables treat reactance as negligible and so does this tool. AWG sizes use the x of the nearest metric size by area. Current rating: tabulated current It from BS 7671 Tables 4D2A and 4E2A (multicore copper, non-armoured, 30 °C reference), ambient factor Ca from Table 4B1, grouping factor Cg from Table 4C1, and Ci = 0.5 for a cable totally surrounded by thermal insulation for 0.5 m or more (Regulation 523.9, applied to the method C rating); the size must have It ≥ In / (Ca × Cg × Ci). The AWG answer is the stock size with at least the copper area of that metric size; NEC Table 310.16 ampacities are set on a different basis and differ. This tool does not check protective device coordination, fault level, earth fault loop impedance, cables in the ground, armoured or single-core cables, or aluminium current ratings. Common voltage drop limits are given in IEC 60364-5-52 Annex G and BS 7671 Appendix 4 (3% lighting, 5% other uses on a public LV supply); these documents give guidance; check the current edition and your local authority. The result is for guidance only and must be checked against the manufacturer's data and the rules that apply to your project.

    Need the end-of-line voltage for a daisy chain of devices? Use the Voltage Drop Calculator. · Techubox Engineering Tools · techubox.com/tools

    To download and print this tool without a watermark, please log in and request approval.

    How to size a cable with this calculator

    On ELV and small power jobs, cable problems usually come from length, not current: a cable that is safe for the current can still deliver too little voltage at the far end. This tool turns the voltage drop limit into a minimum conductor size.

    1. Choose the system voltage: 12, 24 or 48 V DC, 230 V single-phase or 400 V three-phase.
    2. Enter the load current, or the power in watts. On AC, add the power factor so the tool can work out the current.
    3. Enter the one-way route length. The tool counts the return conductor itself, so do not double it.
    4. Set the allowed voltage drop in percent, the conductor material and the conductor temperature.
    5. Leave the current rating check on and enter the installation method, ambient temperature, number of grouped circuits and MCB rating. If a site rule sets a larger size, enter it as the smallest size you will accept.
    6. Read the metric and AWG results, the voltage at the load and the power lost. The drawing redraws as you change the size, cores or cable type.

    The formula behind the result

    For a DC or single-phase circuit the current flows out and back, so the drop is ΔV = 2 × I × L × R / 1000, where I is the current in amps, L the one-way length in metres and R the conductor resistance in Ω/km. For a balanced three-phase circuit the line-to-line drop is ΔV = √3 × I × L × R / 1000. The allowed drop is the percentage times the nominal voltage, so the largest resistance that still passes is Rmax = ΔVmax × 1000 / (k × I × L), with k = 2 or √3.

    Resistance rises with temperature: Rt = R20 × (1 + α(t − 20)), with α = 0.00393 per °C for copper and 0.00403 for aluminium. The tool converts Rmax back to 20 °C and picks the smallest IEC 60228 size whose published maximum resistance is at or below it. The published value is used because a stranded conductor has slightly more resistance than ρ/A suggests. AWG and kcmil use the ASTM B258 diameter formula and ρ/A, so that column is typical.

    On AC the tool adds reactance: ΔV = k × I × L × (R cos φ + X sin φ) / 1000, where cos φ is the power factor. X comes from the x column of BS 7671 Tables 4D2B (PVC) and 4E2B (XLPE), listed from 25 mm²; smaller sizes and DC stay resistive, and AWG sizes use the x of the nearest metric size. If the power factor is unknown, tick the box to use the impedance. Example: 250 A over 150 m at 400 V in 95 mm² PVC multicore drops 15.0 V on resistance alone, 15.7 V at power factor 0.9 (x = 0.135 mV/A/m), and 16.1 V with the tabulated z of 0.43 mV/A/m.

    Worked example: 230 V, 20 A, 30 m, 3%

    A 230 V single-phase lighting feed carries 20 A over a 30 m route, the limit is 3% and the conductor is copper at 70 °C, the full-load temperature of PVC cable.

    • Allowed drop: 3% × 230 V = 6.9 V.
    • Rmax = 6.9 × 1000 / (2 × 20 × 30) = 5.75 Ω/km at 70 °C, which is 5.75 / 1.1965 = 4.81 Ω/km at 20 °C.
    • 2.5 mm² (7.41 Ω/km) fails: the drop would be about 10.6 V, or 4.6%.
    • 4 mm² (4.61 Ω/km) passes: R at 70 °C is 5.52 Ω/km, the drop is 2 × 20 × 30 × 5.52 / 1000 = 6.62 V (2.88%) and the load sees about 223.4 V.
    • In AWG, 12 AWG (3.31 mm²) fails and 10 AWG (5.26 mm²) passes with about 4.7 V (2.05%).

    As a cross-check, the BS 7671 voltage drop figure for 4 mm² two-core 70 °C cable is 11 mV/A/m, and 11 × 20 × 30 / 1000 = 6.6 V, the same answer. A second example: a 24 V DC lock supply of 3 A over 50 m with a 5% limit at 20 °C needs 6 mm² (0.92 V, 3.85%). 4 mm² would drop 1.38 V, or 5.8%, so it fails.

    How the current rating check works

    Voltage drop decides whether the far end gets enough voltage; the current rating decides whether the cable runs cool enough. BS 7671 Appendix 4 tabulates a current It for each size and installation method (B in conduit or trunking, C clipped direct, E free air or perforated tray, A in conduit in an insulated wall) for one circuit in 30 °C air. The cable must have It ≥ In / (Ca × Cg × Ci), where In is the MCB or fuse rating, Ca corrects for ambient temperature, Cg for grouping and Ci for thermal insulation (0.5 if the cable is totally surrounded for 0.5 m or more).

    Heat matters on Gulf projects: at 40 °C, Ca is 0.87 for PVC (70 °C) cable and 0.91 for XLPE (90 °C), and at 50 °C it is 0.71 and 0.82, so the tool starts at 40 °C. Grouping costs more: three circuits bunched give Cg = 0.70, six give 0.57.

    Worked example at 40 °C. 230 V, 32 A, multicore PVC clipped direct, 25 m, 5% limit, 32 A MCB. Voltage drop alone needs 4 mm² (8.8 V). The rating needs It ≥ 32 / 0.87 = 36.8 A: 4 mm² (36 A) fails and 6 mm² (46 A) passes with Iz = 40.0 A, so the current rating decides. Bunched with two other circuits, It ≥ 32 / (0.87 × 0.70) = 52.5 A needs 10 mm² (63 A). The AWG column gives the gauge with at least as much copper (8 AWG for 6 mm²); NEC Table 310.16 ampacities differ. Size for the worst section of the route. These tables give guidance; check the current edition and your local authority.

    AWG and mm² are not the same sizes

    AWG numbers a wire by its diameter: 36 AWG is 0.127 mm across, 4/0 AWG is 11.684 mm, and each step multiplies the diameter by the 39th root of 92, about 1.123. The diameter is d = 0.127 mm × 92(36 − n)/39, where 1/0 to 4/0 are n = 0 to −3. Above 4/0, sizes are given in kcmil, and 1 kcmil = 0.5067 mm². Metric cables are sold by area, so the two series never line up exactly.

    The trap is the near miss. 14 AWG is 2.08 mm², not 2.5 mm², and 12 AWG is 3.31 mm², not 4 mm². If a drawing calls for 2.5 mm² and only AWG stock is on site, the equivalent is 12 AWG, not 14 AWG. The converter and the table under the tool give the exact area, the nearest size and the next size up in the other system.

    What is inside the cable

    The cross-section in the tool and the exploded view below show the same layers. The copper conductor carries the current, and its area sets the resistance. Each conductor has its own insulation, PVC or XLPE, colour-coded so the cores can be told apart. In a multicore cable a filler or bedding keeps the cores round, and the outer sheath protects the whole cable. Only the conductor area affects voltage drop; insulation and sheath set the overall diameter for glands, conduit and tray fill.

    Exploded view of a three-core cableA three-core cable stripped in steps from left to right: 4 the grey outer sheath, 3 the cream filler or bedding, 2 the brown, blue and green/yellow core insulation, and 1 the bare stranded copper conductors at the right-hand end.1234
    Exploded view of a three-core cable, stripped in steps. Drawing for illustration; layer thickness is not to scale.
    1. Conductor: stranded copper (or aluminium). Its cross-sectional area in mm² or AWG sets the resistance and the voltage drop.
    2. Insulation: PVC or XLPE on each core, colour-coded (here brown, blue and green/yellow).
    3. Filler / bedding: keeps the cores round inside the sheath.
    4. Outer sheath: PVC or LSZH, protects the cable and sets the overall diameter used for glands, conduit and tray fill.

    Common mistakes

    • Entering the loop length instead of the one-way length, which doubles the answer.
    • Swapping a metric size for the AWG size with the nearest number rather than the nearest area.
    • Sizing at 20 °C for a power cable that will run fully loaded; use 70 °C for PVC or 90 °C for XLPE in that case.
    • Rating the cable at the 30 °C table value in a hot space, or forgetting the other circuits in the same trunking. The worst section of the route sets the rating.

    Frequently asked questions

    Is this a full cable sizing calculation?

    No. It checks voltage drop and the current rating of multicore copper cable in the common installation methods. Short-circuit withstand, earth fault loop impedance and protective device checks follow the wiring rules for your project, such as BS 7671 or the NEC. These give guidance; check the current edition and your local authority.

    What voltage drop should I allow?

    For 230/400 V installations on a public supply, IEC 60364-5-52 Annex G and BS 7671 Appendix 4 give 3% for lighting and 5% for other uses, from the origin of the installation. For ELV DC equipment, the device’s lowest operating voltage usually decides the limit.

    Why are the metric and AWG answers different areas?

    Each column is the smallest size in its own series that passes. Because the steps differ, the AWG answer can have more or less copper than the metric one.

    How is this different from the Voltage Drop Calculator?

    This tool starts from the drop limit and gives a cable size in mm² and AWG. The Voltage Drop Calculator starts from a cable you have chosen and gives the voltage at each device, including daisy-chained loads and battery end-of-discharge voltage.

    For the power side of the same job, see the UPS & Battery Backup Calculator and the PoE Budget Calculator.